Casa / Produtos / Disjuntor de baixa tensão / Disjuntor em caixa moldada (MCCB) / QM1DC Thermo-magnetic type DC MCCB
Descrição
Technical Data
Product Selection Guide
QM1DC | 125 | H | 2 | 2 |
Product code | Frame size rated current | Rated ultimate short-circuit breaking capacity | Pole number | Release type |
DC circuit breaker | 125, 160, 250,400, 800 | H :higher level type | 2:2-pole 3:3-pole 4:4-pole | 2-short-circuit release 3-complex release |
QM1DC | 125 | H | 2 |
Accessory | Rated operating voltage | External accessory | Wiring method |
0: No 2: Auxiliary contact 3: Complex release | DC 500V-1000V | Null: body operation P: electric operation GZ3: rotary handle | Null: front-board wiring B: back-board wiring C: plug-in type |
Main Performance Indexes
Frame current (A) | 125 | 160 | 250 | |
Model | QM1DС-125H | QM1DС-160H | QM1DС-250H | |
Pole number | 2, 3, 4 | 2, 3, 4 | 2, 3, 4 | |
Rated current (A) | 10,16, 20, 25, 32, 40, 50,63, 80, 100, 125 | 10, 16, 20, 25, 32, 40, 50,63,80, 100, 125, 140, 160 | 100,125,140,160,180, 200, 225, 250 | |
Rated voltage (V) | DC250V, DC500V DC750, DC1000V | DC250V, DC500V DC750, DC1000V | DC250V, DC500V DC750, DC1000V | |
Rated insulation voltage (V) | DC1000V | DC1000V | DC1000V | |
Short-circuit breaking capacity(KA) Icu(Ics=70%Icu) | 250VDC(35KA), 500VDC(25KA) DC750V(15kA), DC1000V(10kA) | |||
Operating cycle number | Electrical life | 6000 | 3000 | 3000 |
Mechanical life | 9000 | 7000 | 7000 | |
Outline dim(mm) a-b-c-ca | 2P | 50-130-68-90 | 60-155-88-115 | - |
3P | 75-130-68-90 | 90-155-88-115 | 105-165-88-115 | |
4P | 100-130-68-90 | 120-155-88-115 | 140-165-88-115 | |
Weight (kg) | 2P | 0.55 | 1 | - |
3P | 0.65 | 1.1 | 1.5 | |
4P | 0.8 | 1.4 | 1.9 | |
Electric operating device (MD) | ● | |||
External driving operating handle | ● | |||
Automatic release | Thermal electromagnetic type |
Frame current (A) | 400 | 800 | |
Model | QM1DС-400M | QM1DС-800H | |
Pole number | 2, 3, 4 | 2, 3, 4 | |
Rated current (A) | 250,315, 350, 400, 630 | 500, 630, 700, 800 | |
Rated voltage (V) | DC250V, DC500V DC750, DC1000V | ||
Rated insulation voltage (V) | DC1000V | DC1000V | |
Short-circuit breaking capacity(KA) Icu(Ics=70%Icu) | 250VDC(35KA), 500VDC(25KA) DC750V(15kA), DC1000V(10kA) | ||
Operating cycle number | Electrical life | 2000 | 1500 |
Mechanical life | 4000 | 4000 | |
Outline dim(mm) a-b-c-ca | 2P | 140-257-103-155 | 210-275-103-155 |
3P | 140-257-103-155 | 210-275-103-155 | |
4P | 184-257-103-155 | 280-275-103-155 | |
Weight (kg) | 2P | 5 | 9.5 |
3P | 5.7 | 12.5 | |
4P | 7.5 | 1.4 | |
Electric operating device (MD) | ● | ||
External driving operating handle | ● | ||
Automatic release | Thermal electromagnetic type |
DC System Protection
System type | Grounding system | Ungrounded system | ||
Various types of reformation | One pole of DC power is grounded | Neutral point of DC power is grounded | ||
Fault A | Max. Isc that only to the positive pole | Isc is close to max. Isc and only to the positive pole, voltage is U/2 | No effect | |
Fault effect | Fault B | Max. Isc that includes two poles | Max. Isc that includes two poles | Max. Isc that includes two poles |
Fault C | No effect | Same as fault A but only to the negative pole | No effect | |
The most serious situation | Fault A | Faults A and C | Fault B | |
Pole breaking | It can be connected at the positive in series, and commonly execute the breaking | At each pole, they must be at U/2 | The two poles to be disconnected are evenly distributed between the two electrodes |
Wiring Method
Un<250V | ||||
Un<800V | ||||
Un<1000V |